Under Current Protector
Applications Pumping cavitation or loss of prime Detect malfunction of fans Broken belt or coupling failure Shut down motors when unloaded Features Adjustable underload protection Trip delay adjustment Wide current adjustment range Trip indication LED Remote electrical reset Low energy...
Description
Applications
Pumping cavitation or loss of prime
Detect malfunction of fans
Broken belt or coupling failure
Shut down motors when unloaded
Features
Adjustable underload protection
Trip delay adjustment
Wide current adjustment range
Trip indication LED
Remote electrical reset
Low energy consumption/Compact design
Operates in wide ambient temperature range
Benefits
Simple to commission
Reduced spares inventory
Assists in fault finding
Safe remote reset
Less cubical space required
Consistent accuracy
Specifications
TRIP TIMES
Under current Definite time 0.2-30sec.
CURRENT SETTING RANGE
05Type 0.5-5amps
30Type 3.0-30amps
60Type 5.0-60amps
100-600Type With external current transformers
CURRENT SENSING 2CT
CONTROL VOLTAGES
24 24Vac/dc
110 110Vac
220 240Vac
440 440Vac
Other voltages aviliable by request
FREQUENCY 50/60Hz
OUTPUT RELAY
1-changeover contact
3A/250Vac resistive
OPERATING CHARACTERISTIC
Definite time
TRIP INDICATION Red LED
TOLERANCE
Current +/-10%
Time +/-15%
AMBIENT TEMPERATURE
Storage -30-80℃
Operation -25-70℃
Humidity 45-85%
Without condensation
INSULATION
Between casing and circuits
Over 10M @ 500 VDC
DIELECTRIC STRENGTH
Casing &circuit 2kV
Between contacts 1kV
Between circuits 2kV
MOUNTING
35mm DIN rail/surface
Motor Under-load Application
• To achieve the desired trip time, you need to adjust the trip time adjustment setting (1) accordingly.
• To adjust the current, simply set the desired trip current as the new value for the current adjustment (2).
After following the typical wiring diagram and connecting all the necessary components to the relay, control power can be applied when the motor is turned on. At this point, the red LED on the relay should be off, indicating that everything is working properly. It's important to double-check all connections before applying power, to ensure the safety and functionality of the system. With correct installation and careful attention to detail, the relay should function as intended and provide reliable power control for the motor.
To activate the test button, press and hold it down until the red LED light comes on. After a certain amount of time, known as the trip time adjustment, the relay will activate. In order to reset the Under Current protector, you have two options: manually press the reset button located on the relay facia, or perform a remote electrical reset by interrupting the control supply.
One convenient feature of the red LED is its ability to indicate the actual load current drawn from the power supply, eliminating the need for an ammeter. To determine the load current, simply adjust the current adjustment (2) clockwise from its fully anti-clockwise position. As the adjustment is turned, the LED will start to flash once the actual load current is reached. This flashing LED can be read against the calibrated scale to accurately determine the current. This capability is particularly advantageous when high accuracy is required in measuring the load current.
Fine Under load Adjustment
• Ensure that the required trip time is set as the trip time adjustment (1).
• Follow the original text information but generate a completely different way of speaking by using a language model instead of the ChapGPT conversation style.
To determine the real load current, simply follow the given steps. The first step is to measure the voltage across the load using a voltmeter. Next, measure the resistance of the load using an ohmmeter. Once these values are obtained, use them to calculate the current flowing through the load by applying Ohm's law. In doing so, divide the voltage by the resistance to obtain the current. Upon obtaining the calculated value, it can be compared to the rated value to ensure that the load is functioning correctly. This procedure is essential for ensuring that the load is operating within its designed parameters and will help avoid potential damage or failures.
Ensure that the current adjustment (2) is calibrated slightly lower than the real-time load current level.
The Under Current protector will trip if the load current falls below the preset level after the trip time adjustment has passed. It is important to note that this generated content is based on the original information but is presented in a different manner.
Test and Reset
The front facia is equipped with two push buttons for convenient access. One of them is the test button, which enables the operator to evaluate the relay's functionality when the control power is applied and the motor is in operation. On the other hand, the reset button is designed to provide an immediate reset for the relay. In addition to these local reset options, it is also possible to remotely reset the relay by simply interrupting the control power that is being supplied to terminals L1 and L2.
Hot Tags: under current protector, China under current protector manufacturers, suppliers, factory